Next jobs
Customers
Jobs
| Date | Customer | Job | Status | Total |
|---|
Pricebook
Recently used
Heating
Cooling
IAQ & Accessories
Comfort Plan
Diagnosing
1Condensate Safety / Clogged Drain
Step 1 β Prove the thermostat is calling
0V: The problem is before the drain safety β check thermostat/control first.
Step 2 β Find the float switch
Step 3 β Test the switch
About 0V across the switch: Switch is CLOSED β signal should be passing through.
Step 4 β Find out WHY it opened
Step 5 β Fix it and prove it
2Outdoor Unit Completely Dead
Step 1 β Check 24V at the contactor coil
0V: The cooling signal is not reaching the condenser β go inside.
Step 2 β Check Y to C at the furnace board
0V here: Check R to C. If R-C has ~24V, suspect thermostat/control. If R-C is 0V, check low-voltage fuse, transformer, furnace power, or board.
Step 3 β If you have 24V, watch the contactor
It pulls in: Move to the 240V test.
Step 4 β Check 240V coming INTO the contactor
0V / no 240V: Go backward β disconnect, fuses, breaker, or wiring.
Step 5 β Check 240V coming OUT of the contactor
240V in AND 240V out: Power circuit is working β move to capacitor, condenser fan motor, and compressor testing.
3Compressor Diagnosis
Step 1 β Prove power is available
No 240V: Stop. The compressor is not the first problem β go back to contactor, disconnect, breaker, or wiring.
Step 2 β Test the compressor capacitor first
Low, 0, or OL: Bad capacitor can make a good compressor look bad β replace capacitor and retest before condemning compressor.
Step 3 β Ohm the 3 compressor terminals
OL on a pair: A winding may be open. If compressor is very hot, let it cool first because the internal overload may be open.
Step 4 β Check if it is grounded
Any resistance / continuity to shell: Compressor is grounded β do not keep energizing it. Compressor is bad.
Step 5 β If electrical tests pass, prove it starts and pumps
Runs, but suction and head barely separate: Possible internal mechanical/pumping failure.
Runs with normal pressure difference and reasonable amps: Compressor itself is probably not the problem.
4Low-Voltage Short / Blowing Fuse
Step 1 β Watch WHEN the fuse blows
Blows only on cooling: Focus on Y and the outdoor-unit circuit.
Blows only on heat: Focus on W/heating controls.
Blows only on fan: Focus on G/fan control.
Step 2 β Remove the thermostat circuit
Fuse stays good: The short is somewhere in the thermostat/control wiring you just removed.
Step 3 β Reconnect one circuit at a time
Example: Everything is fine until Y is energized β chase the cooling/outdoor-unit circuit.
Step 4 β If Y blows the fuse, split furnace from condenser
Fuse still blows: Problem is still on the thermostat/furnace side.
Step 5 β Separate the outdoor wire from the outdoor unit
Fuse stays good: Cable is probably okay β short is inside the condenser control circuit.
Step 6 β Isolate outdoor components one at a time
Fuse still blows: Keep isolating the next 24V branch.
Step 7 β Prove the thermostat itself
5Honeywell / Resideo Zoning Troubleshooting
Step 1 β Start with ONE zone and make a clear call
Zones not calling should normally show CLOSED / closing.
On an HZ311, zone LED green = open/opening, red = closed/closing. A blinking amber zone light points to a thermostat or damper short.
Step 2 β Prove the zone board has good 24V power
0V: Check transformer, fuse, furnace power, wiring.
Voltage drops badly when dampers move: Transformer may be overloaded or a damper/wire may be shorting.
Step 3 β Prove the thermostat call is ENTERING the board
Heating: W to C should be about 24V when that zone calls.
Fan: G to C should be about 24V when fan is called.
24V present: Thermostat/wire successfully delivered the call.
0V: Go backward β thermostat, thermostat setup, loose terminal, broken wire.
Step 4 β See what the board is telling the DAMPER to do
This zone is NOT calling: Board should command it closed. Check M1 to M6; about 24V means the board is telling it to CLOSE.
24V M1-M6 but damper stays open: Bad actuator, broken linkage, stuck blade, or damper wiring.
No closing voltage when it should close: Board/setup/control issue.
Step 5 β Prove whether the DAMPER itself is bad
No power + damper stays closed: Blade/shaft/actuator is mechanically stuck or installed wrong.
Correct 24V close command + actuator does not move: Bad actuator or open damper wiring.
Actuator moves but airflow does not change: Shaft slipped, blade disconnected, blade jammed, or duct issue.
Step 6 β Prove the board is sending the call OUT to the equipment
Heating call: Check equipment W to C β about 24V.
Fan call: Check equipment G to C β about 24V.
Call enters zone board but does NOT leave: Check board setup, DATS/limit condition, purge/timing, or failed panel.
24V leaves the board but equipment does not run: Stop blaming zoning. Troubleshoot the furnace/air handler/condenser normally.
Step 7 β If ALL zones act weird, check DATS, purge and transformer load
HZ311 COOL light blinking: DATS low-temperature limit has been reached.
PURGE light: Board may be in its purge period after a call; do not mistake this for a failed damper/board.
R-C voltage falls when several dampers close: Check transformer VA and damper load. Multiple dampers can be wired in parallel, but the transformer still has to carry them.
Step 8 β Fast symptom cheat sheet
Board sees call, wrong damper position: Test damper output and actuator.
24V M1-M6, damper will not close: Damper actuator / wiring / mechanical bind.
No power and spring-open damper will not open: Mechanical damper problem.
Board sees call but no equipment output: Board setup / DATS / purge / board issue.
Equipment output has 24V but furnace or A/C is dead: Leave zoning and troubleshoot the equipment.
Strong airflow from a zone that should be closed: Verify blade actually closed; check actuator/linkage and damper leakage.
Estimates
Open estimates
Why options
Give the customer a recommended path and a minimum repair without rebuilding the same ticket twice.
Invoices
| Invoice | Customer | Work | Status | Total |
|---|
Job History
Preseason Comfort Plan
Maintenance should give homeowners confidence β not scare them into repairs.
The Preseason Comfort Plan includes one furnace precision tune-up in the fall before heating season and one A/C precision tune-up in the spring before cooling season. At each visit, Kramer Mechanical checks the equipment, explains what is working well, what should be watched, and what actually needs attention. The goal is honest maintenance and planning, not replacing working parts just to create a sale.
π Fall β Furnace
One preseason furnace precision tune-up, safety/operation review, maintenance, and a clear condition report before winter.
π± Spring β A/C
One preseason A/C precision tune-up, operation/performance review, maintenance, and a clear condition report before summer.
Members
Seasonal queue
Expenses
Settings
Business
Square payouts
Live setup: connect the business checking account inside Square. Card, wallet, and ACH payments taken through this software are processed securely by Square and deposited to that account.
Customer Dispatch Profile

Cade Kramer
I started Kramer Mechanical because I wanted to build a company centered on service, truth, and treating people right. My goal is to explain what I find clearly, give you honest options, and never pressure you into work you do not need.
This profile is attached to the βOn My Wayβ customer notification. Live photo delivery requires the approved Infobip MMS sender.
Local data
Start fresh without deleting your customer list. Clear jobs only, or use the full reset if you ever want to remove all locally saved app data.